Power contactor, AC-3 50 A, 22 kW / 400 V 230 V AC, 50 Hz, 3-pole, Size S2, Screw terminal !!! Phased-out product !!! Successor is SIRIUS 3RT2 Preferred successor type is >>3RT2036-1AP00<<
|
|
Product brand name
|
SIRIUS
|
|
Product designation
|
power contactor
|
|
General technical data
|
|
Size of contactor
|
S2
|
|
Insulation voltage
|
|
|
● rated value
|
690 V
|
|
Degree of pollution
|
3
|
|
Surge voltage resistance rated value
|
6 kV
|
|
maximum permissible voltage for safe isolation
|
|
|
● between coil and main contacts acc. to EN 60947-1
|
400 V
|
|
Protection class IP
|
|
|
● on the front
|
IP20
|
|
● of the terminal
|
IP00
|
|
Shock resistance at rectangular impulse
|
|
|
● at AC
|
10g / 5 ms, 5g / 10 ms
|
|
Shock resistance with sine pulse
|
|
|
● at AC
|
15g / 5 ms, 8g / 10 ms
|
|
Mechanical service life (switching cycles)
|
|
|
● of contactor typical
|
10 000 000
|
|
● of the contactor with added electronics-compatible auxiliary switch block typical
|
5 000 000
|
|
● of the contactor with added auxiliary switch block typical
|
10 000 000
|
|
Reference code acc. to DIN EN 81346-2
|
Q
|
|
Ambient conditions
|
|
Installation altitude at height above sea level
|
|
|
● maximum
|
2 000 m
|
|
Main circuit
|
|
Number of poles for main current circuit
|
3
|
|
Number of NO contacts for main contacts
|
3
|
|
Number of NC contacts for main contacts
|
0
|
|
Operating current
|
|
|
● at AC-1 at 400 V
|
|
|
— at ambient temperature 40 °C rated value
|
60 A
|
|
● at AC-1
|
|
|
— up to 690 V at ambient temperature 40 °C rated value
|
60 A
|
|
— up to 690 V at ambient temperature 60 °C rated value
|
55 A
|
|
● at AC-3
|
|
|
— at 400 V rated value
|
50 A
|
|
— at 690 V rated value
|
24 A
|
|
● at AC-4 at 400 V rated value
|
41 A
|
|
Connectable conductor cross-section in main circuit at AC-1
|
|
|
● at 60 °C minimum permissible
|
16 mm²
|
|
● at 40 °C minimum permissible
|
16 mm²
|
|
Operating current for approx. 200000 operating cycles at AC-4
|
|
|
● at 400 V rated value
|
24 A
|
|
● at 690 V rated value
|
12.6 A
|
|
Operating current
|
|
|
● at 1 current path at DC-1
|
|
|
— at 24 V rated value
|
55 A
|
|
— at 110 V rated value
|
4.5 A
|
|
● with 2 current paths in series at DC-1
|
|
|
— at 24 V rated value
|
55 A
|
|
— at 110 V rated value
|
25 A
|
|
● with 3 current paths in series at DC-1
|
|
|
— at 24 V rated value
|
55 A
|
|
— at 110 V rated value
|
55 A
|
|
Operating current
|
|
|
● at 1 current path at DC-3 at DC-5
|
|
|
— at 24 V rated value
|
35 A
|
|
— at 110 V rated value
|
2.5 A
|
|
● with 2 current paths in series at DC-3 at DC-5
|
|
|
— at 24 V rated value
|
55 A
|
|
— at 110 V rated value
|
25 A
|
|
● with 3 current paths in series at DC-3 at DC-5
|
|
|
— at 24 V rated value
|
55 A
|
|
— at 110 V rated value
|
55 A
|
|
Operating power
|
|
|
● at AC-1
|
|
|
— at 230 V at 60 °C rated value
|
22 kW
|
|
— at 400 V rated value
|
38 kW
|
|
— at 690 V rated value
|
66 kW
|
|
— at 690 V at 60 °C rated value
|
66 kW
|
|
● at AC-2 at 400 V rated value
|
22 kW
|
|
● at AC-3
|
|
|
— at 230 V rated value
|
15 kW
|
|
— at 400 V rated value
|
22 kW
|
|
— at 500 V rated value
|
30 kW
|
|
— at 690 V rated value
|
22 kW
|